Learn in your language
Skip to content
IGCSE · Cambridge (CIE) · 0973

Compare transmission losses at matched load power

Use stated receiving voltages and load power to compare current and cable losses without equating source and load power when losses are present.

The transformer · Cambridge IGCSE 0973 · P4.5.6
Exam scope and assessment notes

Mapped to the named 0973 section using teaching from the corresponding single-science course. A 0973-specific review of every Core and Supplement objective is still in progress. Written practice is self-checked; it does not demonstrate supervised laboratory competence or award an official Cambridge grade. This qualification reports two grades on the 9–1 scale; confirm the entry route for your zone and exam series.

Before you begin

  • Use P = IV for a supplied resistive load.
  • Calculate cable I²R losses.

Work on paper. Try each question before revealing help, and explain why your method works.

Quick readiness check

With non-zero cable heating, is source power equal to load power in the steady stated account?

What you will learn

  • Use stated receiving voltages and load power to compare current and cable losses without equating source and load power when losses are present.
  • Compare inverse-current and square-loss scaling with a consistent receiving-point power and source-loss account.
Original comparison keeps receiving resistive load power 200 kW and total loop resistance 5 ohms fixed. At receiving voltages 2 and 10 kV, currents are 100 and 20 A, losses 50 and 2 kW, and source powers 250 and 202 kW with no other losses or net storage. Bars use one common loss scale.Same receiving load: 200 kWReceiving voltage: 2 kVCurrent: 100 ACable loss: 50 kWSource power: 250 kWReceiving voltage: 10 kVCurrent: 20 ACable loss: 2 kWSource power: 202 kWTotal loop R = 5 Ω · common bar scale
Original comparison keeps receiving resistive load power 200 kW and total loop resistance 5 ohms fixed. At receiving voltages 2 and 10 kV, currents are 100 and 20 A, losses 50 and 2 kW, and source powers 250 and 202 kW with no other losses or net storage. Bars use one common loss scale.

Use the voltage at the stated transfer point

A supplied resistive receiving load takes 200 kW. Compare receiving voltages 2000 V and 10000 V, with total transmission-loop resistance 5 Ω in each case. Load current is P_load/V_load: 100 A and 20 A respectively. Cable losses are 100² × 5 = 50000 W and 20² × 5 = 2000 W.

At steady transfer with no other stated losses or net storage, source powers are 250 kW and 202 kW respectively: load power plus cable heating. The given receiving voltages are not silently treated as identical source voltages. This keeps the lower-current heating comparison consistent while delivering the same load power.

Separate loss reduction from ideal transformation

For matched load power and fixed cable resistance, multiplying the receiving voltage by k divides current by k and cable heating by k². Raising receiving voltage fivefold in this exercise reduces loss to 1/25. The reduction is not merely 1/5 because current is squared.

The passive voltage transformation itself does not create the load energy. If cable resistance, load power or operating conditions change too, the simple ratio needs those changes included. The supplied calculations are a model comparison, not real-grid ratings or a safe high-voltage procedure.

Sources for this lesson

Pause and explain

Matched power and resistance, receiving voltage doubled: what happens to cable heating?

Put the idea to work

Worked example

Compare I and cable loss for a 200 kW resistive receiving load at 2000 V and 10000 V, with total loop resistance 5 Ω.

Show the worked solution
  1. Currents are 200000/2000 = 100 A and 200000/10000 = 20 A.
  2. Losses are 100² × 5 = 50 kW and 20² × 5 = 2 kW.
  3. The higher receiving voltage reduces loss to 1/25.

Answer 100 A/50 kW and 20 A/2 kW; higher-voltage loss is 1/25.

Try a topic test

Choose Easy, Normal or Difficult. Save your answers and open worked review after finishing.

Test this topic →

From guided practice to a new situation

Write your answer and reasoning first. Use a hint only if you are stuck. The model solution is for self-checking; your written work is not automatically marked.

1 · Guided

Calculate currents for 200 kW load power at 2000 V and 10000 V.

Give me a hint

Convert kilowatts to watts before using P/V.

Compare my reasoning
  1. 200 kW is 200000 W.
  2. At 2000 V current is 100 A.
  3. At 10000 V current is 20 A.

100 A and 20 A.

Look for these in your work

  • Use receiving voltages.
  • Keep the load power fixed.
2 · Independent

Calculate each cable loss at total R = 5 Ω and those currents.

Give me a hint

Apply I²R separately to each case.

Compare my reasoning
  1. At 100 A, loss is 50000 W.
  2. At 20 A, loss is 2000 W.
  3. Loss ratio is 2000/50000 = 1/25.

50 kW and 2 kW; ratio 1/25.

Look for these in your work

  • Square both currents.
  • Use total resistance once.
3 · Transfer

Find source powers for those steady cases with no other losses or net storage, then explain why 200 kW cannot be both source and load power.

Give me a hint

Include the cable heating in the same system boundary.

Compare my reasoning
  1. Load power is 200 kW in both cases.
  2. Add losses 50 kW and 2 kW.
  3. Source powers are 250 kW and 202 kW.

250 kW and 202 kW; non-zero cable loss requires additional source power.

Look for these in your work

  • Keep the load boundary.
  • Include every stated loss.

Common mistakes

  • Use receiving-point voltage.
  • Keep load power and loop resistance matched.
  • Source supplies load plus loss.
Recall without your notes

What can you explain now?

Why does fivefold voltage reduce matched-power cable loss by twenty-fivefold?

Compare with the explanation

Current is divided by five and loss depends on its square

At fixed transfer power and resistance, the inverse current change is squared in I²R.

After trying it yourself, choose your next review. This is your self-assessment.

Your review choice appears on Today. Sign in to sync it across devices.

Make it stick

Compare inverse-current and square-loss scaling with a consistent receiving-point power and source-loss account.

If you needed the solution, close it and solve the problem again from a blank page. A correct answer is stronger when you can explain the reason for each step.

Keep learning Sciences — Co-ordinated (9-1)

Course scope and assessment

This 9–1 pathway maps all 152 detailed subject-content sections in the published 0973 syllabus for exams in 2028 and 2029. The course map follows the same 2028–2029 section codes as Cambridge's A*–G 0654 syllabus, while keeping 0973's grading and entry rules separate. It adapts lessons from the related single-science courses and excludes clear single-science-only topics. A 0973-specific objective-by-objective review, Core/Supplement audit, human subject-teacher review, supervised laboratory experience and cumulative assessment remain in progress. Written practice is self-checked and does not predict an official grade. The separate 2025–2027 syllabus has not been reconciled here. Cambridge lists 0973 only in a limited number of administrative zones: June in zone 3 and centres in Oman and the UAE; November in zone 3 only. Confirm entry with your centre.

StudyForA · Learn with understanding

Original teaching content and links to official sources. Check your exam year and qualification before using a resource.